FREE SCREEN PRINTED LOGOS ON SWITCH ORDERS OF 20+

Toggle Agent Abort Switch

Toggle Agent Abort Switch

The Toggle Agent Abort switch provides temporary manual intervention by interrupting the agent actuation circuit between the initial alarm and the automatic release of the fire suppression agent. This prevents inadvertent agent discharge, especially in gaseous or clean agent systems. The abort station features a momentary dead-man switch, which when held, opens the actuator circuit by interrupting the electrical current. For added security, this switch features a red safety guard to prevent accidental actuation.

› In the “SYSTEM ON” position, the green LED illuminates.

› In the “SYSTEM ABORTED” position, the red LED illuminates.

Download Toggle Agent Abort Switch cut sheet

Features

  • Provides a momentary toggle switch used to temporarily disconnect the suppression agent by interrupting the actuation circuit for the initial alarm and automatic release.
  • Securely mounted on a two-gang stainless-steel switch plate, operating on 24VDC.
  • Equipped with two LED indicators (Green and Red).
  • Available in both 3-Pole
  • Compatible with both addressable and conventional Fire Alarm systems.
  • Each assembly includes four 6-32” x 1/2” mounting screws and a set of B721 keys.

Additional information

Dimensions 4.5625 × 4.5 × 2.375 in
Switch Rating

Rated 10A 250VAC, 15a 125-250VAC, Dc Rating 15A up to 30VDC

Contact

Form C

LED Rating

10mA each

Operating Temp

32 to 120 F (0-49 C) For Dry Indoor Use

Plate

Stainless steel plate with text silk screened or engraved on plastic

Standards

UL864 9th Edition

CFSM Listed

Installation

Surface Mount installation requires a optional 2.5” deep, compatible back box. Gemcom Part# GEM2GRB

Flush Mount installation requires a two-gang plaster ring on any 4-inch-deep square (1900) back box