Mushroom Abort Switch
The Mushroom Agent Abort switch provides temporary manual intervention by interrupting the agent actuation circuit between the initial alarm and the automatic release of the fire suppression agent. This prevents inadvertent agent discharge, especially in gaseous or clean agent systems. The abort station is equipped with a yellow momentary mushroom-style push button.
› In addressable systems utilizing input modules, the switch is connected with a normally open (NO) contact, which completes the actuator circuit upon pressing.
› In conventional systems, the switch is connected with a normally closed (NC) contact, which breaks the actuator circuit upon pressing.



Features
- Provides a momentary mushroom button that provides a means for temporary manual interruption of the agent actuation circuit between.
- Securely mounted on a two-gang stainless-steel switch plate, operating on 24VDC.
- (1) Standard Normally open contact. Additional contacts available for an additional cost.
- Compatible with both addressable and conventional Fire Alarm systems.
- Each assembly includes four 6-32” x 1/2” mounting screws and a set of B721 keys.
Additional information
| Dimensions | 4.5625 × 4.5 × 3.75 in |
|---|---|
| Switch Rating | 4 amps at 24vdc |
| Contact | (1) Normally open Contact |
| Terminations | Captive Screws with saddles and accept 18-12 AWG wire |
| Operating Temp | 32 to 120 F (0-49 C) For Dry Indoor Use |
| Plate | Stainless steel plate with text silk screened or engraved on plastic |
Standards
UL864 9th Edition
CFSM Listed
Installation
Surface Mount installation requires a optional 2.5” deep, compatible back box. Gemcom Part# GEM2GRB
Flush Mount installation requires a two-gang plaster ring on any 4-inch-deep square (1900) back box